AQUA METRO Technical Data CONTOIL® VZF/A II
Brand: AQUA METRO
Features |
· State-of-the-art-design |
· Electronic counter, mass flow, volume flow indication, multiple output signals |
· Integrated temperature sensor |
· No straight inlets or outlets required |
· Indefendent of viscosity and temperature |
· High vibration resistance |
· Optional; metrological type approval |
· Automatic medium switch based on temperature |
Benefits |
· Mass flow mesurements |
· Highly flexible mounting with ver small space requirements |
· Reliable monitoring and flexible control of the system |
· Accurate measurements |
· A reliable solution with everything from a single supplier |
Simplifies consumption optimzing
Technical data CONTOIL® VZF/A II |
|||||||
Electronic display |
|||||||
Nominal diameter |
DN mm |
15 |
20 |
25 |
40 |
50 |
|
inch |
½ |
¾ |
1 |
1½ |
2 |
||
Max. Medium temperature |
Tmax |
°C |
130, 180 |
||||
Max. Environment temperature |
°C |
−25 to +70 |
|||||
Max. Stroge temperature |
°C |
−25 to +80 |
|||||
Protection class |
rhmax |
% rh |
95, non condensing |
||||
|
IP 66 / IP 68 / IP 69 |
||||||
Total volume / mass |
|
I, m3, G1) |
Max.3 decimals (dynamic) |
||||
kg, t, lb |
|||||||
Resettable volume / mass |
I, m3, G1) |
Max.3 decimals (dynamic) |
|||||
kg, t, lb |
|||||||
Flow rate |
Max.3 decimals (dynamic) |
||||||
Smallest readable amount |
|
|
0.001 |
|
|
|
|
maximum registration capacity |
8 digits |
||||||
Registration time until overrun to zero at |
Qcount (m³) |
>100 years |
|||||
Data preservation |
|
|
by non-volatile memory (EEPROM) |
Outputs |
|
||||
3 (2 pulse / frequency, 1 analog 4-20 mA) |
|
|
freely selectable, totally independent of each other |
||
pulse output |
|
|
volume or mass pulse 0-200 pulse/sec.(50% duty cycle) |
||
Current 4-20 mA |
|
|
volume flow, mass flow or temperature signal |
||
Frequency |
Qmin, Qmax |
volume flow, mass flow or temperature minimum |
|||
maximal and hystersis paramerized |
|||||
Limit switch |
Qlimmax, Qlimmin |
allows you to set an alet whenever predefined |
|||
flow rates are exceeded (NC/NO) |
|||||
Flow meter state switch |
Alarm, Error |
state and on/of parameterized (NC/NO) |
Electronic |
||
Power supply |
VDC |
6 − 30 |
Quiescent current zero |
mA |
4 |
Relais output |
|
|
Switching element |
solid state relay (out1 & out2) |
|
Resistance ON |
Ω |
≤40 |
Resistance OFF |
MΩ |
≥10 |
Max. Supply voltage |
VDC |
≤48 |
Max. Switching current |
mA |
≤50 |
Pulse width |
ms |
2-500 (dynamic) |
Pulse frequency |
Hz |
0 - 200 |
Current output |
|
|
Analog output |
mA |
4 - 20 passive |
Resolution |
bit |
26 |
Max. Error |
mA |
±0.2 |
Update interval |
s |
<0.1 s |
Maximum Load (RL) |
Ω |
0 to 1116. depending on external supply voltage |
of the power supply unit U-6 |
||
_____ Ω;(e.g.: 1116O@30V) |
||
0.0215 |